| INDUSTRY | APPLICATION |
| Power & Energy | PCS/BMS communication and intelligent video monitoring |
Introduction
A centralized battery energy storage station in Yunnan, China needed one communication architecture for BMS serial data, PCS-related plant connectivity, and intelligent video monitoring. The design used A/B industrial Ethernet rings, local RS-485 conversion, and PoE access to reduce single-path exposure and simplify the field network.
The 100 MW/200 MWh centralized energy storage station is located at a Power Plant in Yunnan. Its principal equipment includes battery systems, power conversion systems (PCS), and step-up transformers. During charging, the PCS converts AC power to DC for storage; during discharge, it converts stored DC power back to AC for the grid.
The communication network supports two operational data types at the field level: BMS status from battery containers and video streams from monitoring cameras. The video system is also intended to associate images with equipment parameters such as temperature for event analysis.
Battery-container BMS devices expose RS-485 data, while the station’s supervisory network uses standard TCP/IP. Without an industrial conversion layer, the control system cannot collect that data through a consistent Ethernet interface.
Video monitoring introduced a second infrastructure requirement: cameras needed both network access and field power. Building separate communication, camera-power, and serial-integration systems would increase cabling, cabinet space, and the number of components maintenance teams must trace.
Requirements
The network had to support a large, distributed equipment population while avoiding a single communication path for critical plant data. A repeatable architecture was needed so that installation, configuration, and maintenance effort did not grow unpredictably with every battery container and monitoring point.
- Convert BMS RS-485 data to standard TCP/IP for real-time acquisition.
- Provide A/B redundant industrial Ethernet paths using a managed ring architecture.
- Deliver power and data to IP cameras through PoE.
- Support video association with operating parameters such as temperature.
- Operate across -40°C to 75°C in a power-system environment.
Solution
The communication backbone uses 100 MISCOM7210G managed industrial Ethernet switches to form A/B redundant rings with the MW-Ring protocol. The two paths reduce dependence on a single link and create a consistent station-wide structure for PCS/BMS-related traffic.
MPort3100 Series serial device servers convert battery-container RS-485 data into Ethernet near the BMS source. More than 70 MISCOM7210GP managed PoE switches provide both Gigabit connectivity and power to monitoring cameras. This combination separates the field-interface problem into three clear roles: resilient transport, serial integration, and powered video access.
Deployment and Verification
Deployment distributed managed switches across the station to create the A/B ring paths, placed serial conversion close to the battery-container BMS interfaces, and installed PoE switching at camera access points. The source brief records 100 MISCOM7210G units and more than 70 MISCOM7210GP units.
Verification focused on BMS RS-485-to-Ethernet data continuity, reachability through both ring paths, PoE camera power and data, and the availability of video associated with equipment parameters. The source does not publish measured ring-recovery time, packet loss, or commissioning duration; those figures are therefore not claimed in this case.
Featured Products
Results
The A/B ring design reduced exposure to a single failed communication path. Edge conversion prevented BMS serial integration from becoming a central custom-gateway problem, while PoE removed the need for separate camera power cabling at each monitoring point.
- Lower single-link risk through independent A/B managed ring paths.
- Less protocol-integration effort through standardized RS-485-to-Ethernet conversion.
- Reduced camera installation complexity by carrying power and data over one Ethernet cable.
- Clearer maintenance boundaries between the backbone, BMS conversion layer, and video access layer.
- A repeatable deployment pattern across more than 170 industrial switch locations.
Maisvch can help define redundancy boundaries, serial-integration points, PoE budgets, and commissioning criteria for utility-scale battery energy storage networks. Contact now!