8×Digital Inputs, 8×Digital Outputs, 1×RS232/485 Serial Port
The Maisvch MW-IOD0808 is a Modbus RTU remote I/O module for monitoring eight digital input states and controlling eight relay outputs from a Modbus RTU master. It provides one RS232 or RS485 serial interface, with baud rates from 600 bps to 460800 bps.
The module provides input filtering and edge counting, configurable relay power-up states and output hold timing, momentary close or open commands, and cyclic switching at a configured frequency. Device information, online restart, factory reset and firmware upgrade functions are available, and remote I/O configuration software supports commissioning and configuration. A 9–36 VDC input, −40°C to +85°C operating range, and 35 mm DIN-rail or wall mounting suit industrial automation, building automation, environmental monitoring, energy management, safety monitoring and industrial IoT installations.
| Software | |
| Management Function | Support Modbus RTU protocol, Slave address (1-247) setting and reading
Support Modbus function codes 01, 02, 03, 04, 05, 06, 15, 16 Support DI status reading, DI input filtering, DI counting. Supports DO status reading and control, DO power-on initial state setting, DO output delay hold Support serial port parameter reading and setting Support device information reading Support online reboot, factory reset, device upgrade. Support remote IO configuration software management |
| Interface | |
| Serial Port | Serial port type: 1 RS232 or RS485 optional
Connection: 6-position 5mm pitch terminal block Baud rate: 600bps~460800bps Data bit: 8bit Stop bit: 1bit, 2bit Check digit: None, Odd, Even Isolation voltage: 500VDC |
| DI | Number of channels: 8 digital inputs
Connection: 10-position 5mm pitch terminal block Modbus function code: 02, 03, 04, 16 Rated voltage: DC12V (DC5~24V) Input Type: Wet contact PNP (Logic level 0: No external power input; Logic level 1: with DC5~24V external power input) Isolation protection: 500VAC (optocoupler isolation) |
| DO | Number of channels: 8 digital outputs (DO1-DO4 are 3-contact relays, DO5-DO8 are 2-contact relays)
Connection: 20-position 5mm pitch terminal block Modbus function code: 01, 03, 04, 05, 15Output type: relay output (dry contact) Contact rated load: 10A@AC250V, 10A@DC30V Initial insulation resistance: 1000MΩ (min.) @500VDC Contact resistance: ≤100mΩ Electrical life: 100,000 operations (rated load) Isolation protection: 500VAC |
| Button | One-click restart, factory reset |
| Status LED | Operation, DO status |
| Power Supply | |
| Input Voltage | DC9~36V |
| Power Consumption | <3.5W@DC24V(full load) |
| Connection | 2-position 5mm pitch terminal block |
| Protection | Anti-reverse |
| Physical Characteristics | |
| Dimensions | 145×90×40 mm (Not including DIN rail mounting clip or connectors) |
| Installations | 35mm DIN Rail mounting or wall mounting |
| Shell | Plastic |
| Weight | 0.25kg |
| Working Environment | |
| Operating Temp | -40℃~+85℃ |
| Storage Temp | -40℃~+85℃ |
| Relative Humidity | 5%~95%(non-condensing) |
| Industry Standard | |
| EMC | IEC 61000-4-5(Surge): Level 3 |
| datasheet | ||
|---|---|---|
| MW-IOD0808 Datasheet | MW-IOD0808-datasheet | V1.0 |
| Standard Model | RS232/485 | DI | DO | Input Voltage |
| MW-IOD0808 | 1 | 8 | 8 | DC9~36V |